Butterfly, gate, guillotine and diverter dampers do different jobs. Pick the wrong one and you lose either control accuracy or tight shut-off. This guide compares them side by side.
At a glance
Type | Motion | Best for | Watch out for |
|---|---|---|---|
Butterfly / louvre | Blade rotates on a shaft | Regulation and general isolation | Blade stays in the flow; moderate leakage |
Gate (slide) | Blade slides across the duct | Isolation with a clear flow path | Needs side space; dust can jam guides |
Guillotine | Blade lifts out of the duct | Positive isolation for maintenance | Tall, slow, not for modulation |
Diverter | Blade or flap swaps the flow path | Switching between two ducts | Thermal distortion; sealing in both positions |
Back-draft | Self-acting blades | Preventing reverse flow | Not a control device |
Inlet vane | Radial vanes at fan inlet | Fan flow control | Needs fan-specific design |
Butterfly damper
The blade turns on a central or offset shaft. It is the simplest and most economical option and handles both regulation and isolation. The trade-off is that the blade stays in the gas stream even when fully open, adding some pressure drop. Multi-blade louvre versions suit large rectangular ducts. Opposed-blade louvres generally give more precise flow control, while parallel blades suit mostly open-or-closed duty.
Gate (slide) damper
A flat plate slides across the duct. When open, the flow path is clear, so pressure drop is low. It needs room beside the duct for the blade to travel, and dust packing in the guides can cause sticking. Specify purged or sealed guides for dirty service.
Guillotine damper
The blade lifts completely out of the gas path, so you get positive isolation for maintenance entry. Double-blade designs with a seal air system are common on flue gas ducts, and manufacturers offer low-leak and zero-leak versions, because pressurised air in the gap between the blades blocks gas leakage. Guillotine dampers are slow and tall, and are for isolation only, not for modulating flow.
Diverter damper
A diverter sends flow into one of two ducts, for example from a boiler to the main stack or to a bypass stack. It must seal on both positions and survive repeated thermal cycles. Expect heavier construction, stiffening and, on hot gas, seal air.
Back-draft and inlet vane dampers
Back-draft dampers are self-acting. Forward flow pushes the blades open and gravity or counterweights close them when flow stops or reverses. They protect idle fans in parallel systems from recirculation. Inlet vane dampers (inlet guide vanes) pre-swirl air into the fan wheel. At part load they typically use less power than throttling with an outlet damper, which is why inlet control is widely used on large ID and FD fans.
Quick selection rules
- Need modulating control on a duct: butterfly or louvre.
- Need tight isolation for maintenance: guillotine with seal air.
- Need low pressure drop when open and simple isolation: gate damper.
- Need to switch between two paths: diverter.
- Need to stop reverse flow without power: back-draft.
- Need fan power savings at part load: inlet vane.
Whatever the type, confirm medium, temperature, dust load, permissible leakage and actuator requirements before ordering. ANSI/AMCA 510 covers test methods for heavy-duty industrial dampers, while AMCA 500-D and 511 are the usual references for commercial and HVAC dampers.
Share your duct details with Freture Techno's engineers and we will recommend the damper type, material and actuation that match your duty.